- Overview
- Product Description
- Technical Data
- Installation Instructions
- Picture in Real Site
- FAQ
- Company Profile
Basic Info.
Model NO.
AMB100-A
Theory
Electronic Meter
Power Meter Connection
Terminal
Measured Signal
Continuous Wave
Type
Energy Meter
Certification
RoHS, ISO, CE
Customized
Customized
Rated Voltage
3*220/380VAC
CT
Amb100-a 5A/2.5mA 100A/20mA 400A/100mA 600A/100
Overloading
1.2
Input Frequency
45-65Hz
Auxiliary Power Supply
Triggered Upon Receipt of Request Signal
Communication
RS485/Modbus-RTU or Lora Antenna
Installation1
DIN35mm Rail
Transport Package
Carton
Specification
170*150*130mm
Trademark
Acrel
Origin
China
HS Code
8501109190
Production Capacity
5000
Product Description
AMB intelligent bus AC monitoring device
AMB intelligent bus AC monitoring device is a new development to cater for smart power bus bar. It consists of a feeding detection module and a tapping detection module and integrates functions of conventional power measurements, electricity monitoring, consumption assessment and control. It also boasts the online alarm function and enables the independent off-line operation. It monitors the bus bar interface temperature in real time. By virtue of 2 RJ45 communication ports (1 in and 1 out) and MODBUS-RTU protocol, it is easy and reliable to upload the monitoring data to the touch screen of the main controller for centralized monitoring, ensuring safe and reliable operation of the system. The smart bus bar monitor has several benefits such as flexible and convenient wiring so that it is a good substitution of the traditional centralized array cabinet.
Measured parameters | Voltage, current, frequency, active power, inactive power, power factor, active energy, inactive energy, 2nd-63rd harmonic, temperature, leakage | |
Voltage | Rated value | 3x220/380VAC |
Range | ±20% | |
Overloading | 1.2 times than the rated voltage value continuously or 2 times than the rated voltage value instantaneously per second | |
Current | CT | AMB100-A:5A/2.5mA, 100A/20mA, 400A/100mA, 600A/100mA AMB110-A:100A/20mA |
Range | 1%-120% | |
Overloading | 1.2 times than the rated current value continuously or 10 times than the rated current value instantaneously per second | |
Input frequency | 45-65Hz | |
Measurement accuracy | Voltage/current:grade 0.2; active power/energy:grade 0.5; inactive power/energy:grade 1; temperature:±1ºC | |
Auxiliary power supply | AMB100/110-A(/W):triggered upon receipt of request signal AMB100/110-A(/W)-P1:follow the bus bar voltage | |
functions | Temperature detection | -20-150ºC |
Leakage | 0-1A | |
Digital input | 2 dry-contact inputs | |
Digital output | 2 relay outputs; contact capacity:3A/30VDC, 3A/250VAC | |
Communication | Via RS485/Modbus-RTU or LORA antenna | |
Installation | Use DIN35mm rail | |
Protection | IP20 | |
Pollution level | 2 | |
Environment | Temperature/ humidity/ altitude | Working temperature:-20-60ºC Storage temperature:-25-70ºC Relative humidity:≤93% Altitude:≤2500m |
Safety | Insulation | The minimum insulation resistance between all terminals and conductive components of the shell is 100MΩ. |
Withstanding voltage | When a voltage of 2kV AC is applied between the voltage/ current input, relay output, RS485 port, auxiliary power supply and digital inputs, the leakage shall be less than 2mA and no breakdown or flashover shall occur in 1min.. | |
Electromagnetic immunity | Electrostatic discharge immunity | Class 4 |
Radio frequency electromagnetic immunity | Class 3 | |
Transient burst immunity | Class 4 | |
Surge immunity | Class 4 |