- Overview
- Feature
- Specification
- Application
- Company Profile
- Certifications
- Our Service
- FAQ
Basic Info.
Model NO.
AFR-M
Electricity Type
Ac
Number of Pole
3
Load
Medium Power Relay
Protective Characteristics
Open Relay
Action Principle
Electromagnetic Type
Size
Miniature
Type
Electric Parameter Relay
Transport Package
Carton
Specification
10*10cm
Trademark
Blue jay
Origin
China
Production Capacity
1000PCS Per Month
Packaging & Delivery
Package Size
10.00cm * 10.00cm * 10.00cm
Package Gross Weight
0.650kg
Product Description
Arc protection relays are mainly used to detect arc faults in electrical systems and protect equipment and personnel in electrical systems from arc faults. Arc protection relays can detect arcs by monitoring parameters such as current, voltage, and electric power, and quickly disconnect the power supply before an electrical fire occurs, thereby reducing the risk of fire.
Arc protection relays are usually used in medium and high-voltage power distribution systems, control cabinets, transformers, generators, motors and other electrical equipment. They adopt the dual-criteria principle of arc light detection and overcurrent detection and have the characteristics of fast protection action and high reliability.
* Comprehensive record of fault information;
* Double criterion of over-current and arc, high reliability;
* Optical fiber transmits, strong electromagnetic interference resistance;
* Programmable logic of trip exit;
* Fast exit tripping, short total fault clearing time.
-. Electrical parameters tolerance
-. Arc signal input
-. Relay output
-. Digital input
Note: Optional passive node (confirm before order)
-. Action time tolerance
Pure arc protection: ≤10ms
Double criterion protection: ≤20ms
-. RS485 communication
-. Ethernet communication
-. Environment
-. Electromagnetic compatibility
* Complete digital design, simple principle;
* Strong electrical performance;* Comprehensive record of fault information;
* Double criterion of over-current and arc, high reliability;
* Optical fiber transmits, strong electromagnetic interference resistance;
* Programmable logic of trip exit;
* Fast exit tripping, short total fault clearing time.
-. Power supply
AC/DC85 ~ 265V
-. Consumption
≤ 8W
-. Current input
Current rated : | 5A/1A |
Measurement range: | protection current: 0~20In |
Consumption: | ≤ 5VA |
-. Electrical parameters tolerance
Protection current: | ≤ 2% |
Protection frequency: | 0.1Hz |
-. Arc signal input
Channels number: | 12-48 channels (optional) |
Sensor type: | Optical fiber |
Detect light type: | Visible light/UV light (optional) |
-. Relay output
Channels number: | 9 channels |
Operating Voltage: | AC250V/8A |
Input method: | Passive contact |
Isolation method: | Photoelectric isolation, isolation voltage 2500V |
Relay action cycle: | <4ms |
-. Digital input
Channels number: | 16 channels |
Operating Voltage: | 220Vdc |
Input method: | Wet contact |
Isolation method: | Photoelectric isolation, isolation voltage 2500V |
-. Action time tolerance
Pure arc protection: ≤10ms
Double criterion protection: ≤20ms
-. RS485 communication
Interface: | RS485 (one standard, two optional) |
Isolation type: | photoelectric isolation, lightning protection |
Baud rate: | 9600bps |
Protocol: | Modbus |
-. Ethernet communication
Interface: | 2-Way Ethernet optional |
Network parameters: | 10M/100M adaptive |
Default IP: | 192.168.12.2/192.168.13.2 |
Standard: | IEC60870-5-103 |
-. Environment
Working environment: | -10 ~ 55°C/ < 93% RH (Non-condensing) |
Storage environment: | -30 ~ 70°C/ < 70% RH (Non-condensing) |
Relative humidity: | 5%~ 95% |
Atmospheric pressure: | 60kPa ~ 106kPa |
-. Electromagnetic compatibility
Item | Standard |
Electrostatic discharge test: | IEC 60255-22-2:2008. level-4 |
Fast transient dry resistance test: | IEC 60255-22-4:2008. level-A |
1mhz burst interference test: | IEC 60255-22-1-2007. level-3 |
Electrical disturbance test: | IEC 60255-22-2:2008.level-3 |
Surge immunity test: | IEC 60255-22-5:2008 |